Increasing the filter setting time increases the effectiveness of the noise prevention, however, this also increasingly slows drive
response time.
No.
Name
Setting Range
Default
H6-05
Pulse Train Input Filter Time
0.00 to 2.00 s
0.10 s
n
H6-06: Pulse Train Output Terminal MP Monitor Selection
Selects the pulse train monitor output terminal MP function. The set value
ooo
is equal to the numerals in U
o
-
oo
of the
selected monitor.
Refer to U: Monitors on page 399
for a complete list of monitors. Selectable monitor items are listed below.
No.
Name
Setting Range
Default
H6-06
Pulse Train Output Terminal MP Monitor Selection
000, 031, 101, 102, 105, 116,
501, 502, 801 to 809
102
n
H6-07: Pulse Train Output Terminal MP Monitor Scaling
Pulse train monitor scaling sets the output frequency at terminal MP when the monitor item is 100%. Set H6-06 to 102 and
H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.
No.
Name
Setting Range
Default
H6-07
Pulse Train Input Monitor Scaling
0 to 32000 Hz
1440 Hz
5.7 H: Terminal Functions
212