38
CleanFire Owners Manual
2016
Troubleshooting
Error Codes
Below is a list of errors that the controller can display and the course of action that should be taken to rectify the
issue. All repairs must be made by qualified persons.
Error
Cause
Solution
O2 Error
O2 Reads 0% for 60 consecutive
minutes
Disconnect power and check the O2 sensor connec-
tions.
Remove the O2 sensor and check for damage.
Calibrate the 02 sensor as described in the opera-
tion section.
If none of these work, replace the O2 sensor.
O2 Reads Over 18% while Catalytic
Convertor is above 650
˚F for 60
consecutive minutes
RTD Error
RTD Reads -40˚F or 248˚F
Disconnect power and check the RTD Connections.
If this does not work, replace the RTD Probe.
TC Error
Thermocouple reads less than
-100˚F
Disconnect the power and check the Thermocouple
connections.
If this does not work, Replace the Thermocouple.
Catalytic Convertor thermocouple
Reads same as board temperature
+/-1˚F for 5 consecutive minutes
Snap Error
Snap disc triggered or low water
cutoff has triggered.
Wait for boiler too cool, thus allowing the snap disc
to reset. If the boiler does not reset, replace the
snap disc.
Check the door seals for leaks.
Check the pump for proper flow.
Adjust the draw on the stove or the wood load.
Check the water pressure in the boiler. If low, add
water.
Fan Error
Fan torque applied but not getting
tach signal
Disconnect power and check the fan connections.
If the connections are not the cause, disconnect
power, allow the boiler to cool, and remove the
fan to inspect for damage or creosote/ash buildup.
Clean if needed.
If damage to the fan is found, or if the fan still fails
to work, replace the fan.
If none of these suggestions appear to solve your problem, contact your dealer.