8. Setting of parameters
Page 82
105204
– WTS-300-E - V4.1 - 20.01.2022
Section 8.3
: Level “Extended cooling parameters” (P parameters)
Alarm “Water detection in cleaning pipe”
Range
Default
Alarm / prevention of water intake into tank during
cooling mode
(see also section 10.4)
P40 Alarm activation level monitoring 1 / 2 in
cooling mode
If the level electrode detects water in the
cleaning pipe during cooling mode:
0 .. 4
0
0: deactivated = no consequence
1: activates fault indication [F52] when level 1 is reached
2: as 1, plus outlet valve 1 opens
3: activates fault indication [F52] when level 2 is reached
4: as 3, plus outlet valve 1 opens
Alarm „tank overflow protection“
Explanation see section 10.7
Range
Default
P42 Activation tank overflow protection
0 .. 4
0
0: deactivated
1: Level switch
“tank full” – signal applied = alarm
2: Level switch
“tank full” – no signal = alarm
3: In case of activated litre recording [A54]:
Achievement of litres [P43] entered, triggers alarm.
4: Detection at level input 2 triggers alarm.
P43 Maximum filling quantity in litre
input in hectolitres (=100 l)
0...500 (is equivalent to 0 to 50.000 litres)
0 .. 500
100