8. Setting of parameters
Page 104
105204
– WTS-300-E - V4.1 - 20.01.2022
8.9
Level “Extended tank monitor parameters” (H parameters)
Don‘t add milk - temperature conditions
Fault
Range
Def.
H10 Milk temperature too high for too long
F1
0 .. 50,0 °C 13,0
H11 Time limit for [H10] *
0 .. 999 min. 600
H12 Milk temperature too high for too long
F2
0 .. 50,0 °C 16,0
H13 Time limit for [H12] *
0 .. 999 min. 360
H14 Milk temperature too high for too long
F3
0 .. 50,0 °C 28,0
H15 Time limit for [H14] *
0 .. 999 min. 300
Power failure times
H19 Temperature limit for fault F6
0 = temperature-independent
F6
0 .. 50 °C
7,0
H20 Max. power failure time in cooling mode *
F6
0 .. 999 min. 300
Cleaning temperature monitoring
H30 Minimum cleaning temperature *
F11
0 .. 50,0 °C 40,0
H31 For min. time *
F12
0 .. 999 min.
2
Agitator monitoring
H40 Agitator fault in cooling mode -
no stirring of milk *
F15
0 .. 999 min. 450
H41 Timeout "No agitator" *
F16
0 .. 999 min.
60
H42 Min. run time agitator
[zu H41]
F16
0 .. 500 sec.
60
* 0 = deactivated
Switch to level
“Extended tank monitor
parameters”
See section 8.1
H parameters
Code: F94A
Working level
for normal daily operation
General cooling parameters
code: C212
Extended cooling parameters
code: D345
General cleaning parameters
code: B454
Extended cleaning parameters 1
code: C567
Extended cleaning parameters 2
code: D432
Service parameters
code: EA03
General tank monitor parameters
code: 4711
Extended tank monitor parameters
code: F94A
Alarm configuration
code: FFFF
Configuration
code: A384
I/O test parameters
code: 10E5