12. Other information - Tank monitor
105204
– WTS-300-E - V4.1 - 20.01.2022
Page 151
12.
Other information - Tank monitor
12.1 Activation delay tank monitor [H90]
The activation delay of the tank monitor is required to test the operation modes dur-
ing the commissioning without activating false alarms.
The delay is activated when the WTS-300 is switched on.
- All time-dependent alarms are temporarily deactivated
- Only after the set time [H90] has elapsed the tank monitor is set to the basic
condition and activated.
- After one day, parameter [H90] is also reset to 0 to prevent a repeated delay.
12.2 EMAIL-, alarm + remote maintenance module ESIPM
The email alarm and remote maintenance modem ESIPM-001 is used
- to send fault messages by email
- for remote configuration
- for remote diagnosis
- for configuration and diagnosis via the own LAN / WLAN network
of the connected controllers.
For proper installation, please pay attention to the
Configuration:
Activation of alarm module monitoring => Parameter [A73]
12.3 SMS, alarm + remote maintenance module ESGSM
The SMS alarm and remote maintenance modem ESGSM-001 is used
- to send fault messages by SMS
- for remote configuration
- for remote diagnosis
of the connected controllers.
For proper installation, please pay attention to the
Configuration:
Activation of alarm module monitoring => Parameter [A73]