6. Cleaning
105204
– WTS-300-E - V4.1 - 20.01.2022
Page 47
Section 6.4: Parameterization of the cleaning stages
Cleaning agent dosing:
(see also section 6.3.6)
Depending on the setting of the parameter [r20], detergent is injected at the end of
the water intake time [n32] or the subsequent water intake time [n33] as follows:
If ‚cleaning stage 5' is activated [r45=1] only alkaline detergent is injected here
for duration [n101*].
If 'cleaning stage 5' is deactivated [r45=0] alkaline detergent is injected x times
for duration [n101*] before acidic detergent is injected once for duration [n102*].
The number of alkaline cleaning cycles is set in [r21].
If a heater is present [r35], this is switched on. When the heating temperature
[n106] is reached, the heater is switched off again.
If the temperature is not reached within the pre-set time [r37], the control unit con-
tinues with the program, but a fault report is displayed at the end. See section 7.5.3
- F44
If a switch-on delay [r36] has been parameterized for heating, heating starts only
after this time has elapsed. (This is to ensure that water is in the heater.)
Main circulation time: The water circulates for the pre-set time [n34]. During the
main circulating time, a post-heating temperature [n109] can be defined.
An additional time can be defined in parameter [n35], in which the drain valve
opens (agitator and cleaning pump continue to run)
Agitator and pump switch off.
Drain valve opens for the pre-set time [n36]. See also [n35].
In case of green
n32 and n33 have to be
parameterized on „0“