7. Setting of parameters
Page 58
105466
– TW-31-E - V1.9 - 06.04.2021
7.9
Ebene “I / O test parameters” (o- parameters)
Meaning of the parameters
All inputs and outputs of the individual components can be tested in this parameter
level. For this purpose the corresponding relays are set to 'I' or '0'.
This operating level is NOT reset automatically!
Test of relay outputs
Range
Def.
Switched on relays remain switched on until they are reset
manually.
o.1 Test relay 1
0 .. 1
0
o.2 Test relay 2
0 .. 1
0
o.3 Test relay 3
0: On
1: Off
0 .. 1
0
Switch to level
“I / O test parametert” see section 7.2
o. parameters
Code: 10E5
Working level
General tank monitor parameter
Code: 4711
Extended tank monitor parameter
Code: F94A
Alarm configuration
Code: FFFF
Hardware configuration
Code: A384
Sensor adjustment
Code: C212
Service parameter
Code: EA03
I/O test parameter
Code: 10E5