7. Setting of parameters
105466
– TW-31-E - V1.9 - 06.04.2021
Page 53
to section 7.6:
Level “Hardware configuration” (A- parameters)
Assignment of output functions to relays K1 to K3
0: deactivated
1: Alarm tank monitor
2: Alarm in general
3: Texternal alarm light
Setting
Def.
A1
A2
A3
assignment relay K1
assignment relay K2
assignment relay K3
0 .. 3
0 .. 3
0 .. 3
1
2
3
Assignment of input functions to digital inputs DE1 to DE12
0: deactivated
1: Cooling mode detection
2: Cleaning mode detection
3: milk intake detection
4: without function
5: without function
6: without function
7:
Float switch ‚alkaline’
8:
Float switch ‚acidic’
9: without function
10: without function
11: thermal protection compressor
12: without function
13: Agitator detection 1
14: Agitator detection 2
Setting
Def.
A21
A22
A23
A24
A25
A26
assignment digital input DE1
assignment digital input DE2
assignment digital input DE3
assignment digital input DE4
assignment digital input DE5
assignment digital input DE6
0 .. 14
0 .. 14
0 .. 14
0 .. 14
0 .. 14
0 .. 14
1
2
3
4
5
6
A27
A28
A29
A30
A31
A32
assignment digital input DE7
assignment digital input DE8
assignment digital input DE9
assignment digital input DE10
assignment digital input DE11
assignment digital input DE12
0 .. 14
0 .. 14
0 .. 14
0 .. 14
0 .. 14
0 .. 14
7
8
9
10
11
12
* The relay functions for
assignment 1 and 2 are
configured in parameters
A45 and A46.
230V AC
wiring only with L1
Connect potential-free
contacts to terminal 38