7. Setting of parameters
105466
– TW-31-E - V1.9 - 06.04.2021
Page 57
7.8
Level “Service parameters” (E- parameters)
These parameters are only used to query ACTUAL states.
Display tank monitoring time counter and values
Range
Def.
Display of...
E1 ... over- / under time temperature / time 1
0…900 min. - - -
E2 ... over- / under time temperature / time 2
0…900 min. - - -
E3 ... over- / under time temperature / time 3
0…900 min. - - -
Based on the error messages F1 - F3, it can be read
here how long the milk temperature has already been
above the respectively set limit value.
E6 ... the last cleaning temperature reached
Displays the maximum temperature during the last
cleaning cycle.
0…99,9 °C
- - -
E15 ... accu voltage
Display the current accu voltage
(Only if optional accu pack is installed)
0,0V..12,0V
- - -
E50 SIM PIN entry for optional ESGSM
for optional remote maintenance module
-1..9999
- - -
-1
= no PIN deposited
0000 … 9999 = SIM PIN
Switch to level
“Service parameters” see section 7.2
C parameters
Code: EA03
Working level
General tank monitor parameter
Code: 4711
Extended tank monitor parameter
Code: F94A
Alarm configuration
Code: FFFF
Hardware configuration
Code: A384
Sensor adjustment
Code: C212
Service parameter
Code: EA03
I/O test parameter
Code: 10E5