7. Setting of parameters
105466
– TW-31-E - V1.9 - 06.04.2021
Page 49
to section 7.4:
Level “Extended tank monitor parameters” (H parameters)
Monitoring of cleaning temperature
Fault
Range
Def.
H30 Minimum cleaning temperature
F11
0..50,0 °C 40,0
H31 Minimum exposure time detergent
Exposure time at cleaning temperature [H30]
0: deactivated
1…999: Minimum exposure time in minutes
F12
0..999 min.
2
H32 Minimum cleaning time (detection of stop)
Alarm is activated, when cleaning stops before
the set time [H32].
F13
0..300 min.
35
Monitoring of agitator
Fault
Range
Def.
H40 Agitator error in cooling mode
No milk detection by agitator detection module
after X minutes
F15
0..999 min. 450
H41 Timeout “No agitator”
No stirring of the milk in cooling mode X minutes
after the last agitator stop
F16
0..999 min.
60
H42 Minimum running time of agitator
Alarm is activated when agitator has run less
than X seconds.
F16
0..500 min.
60
H43 Delay monitoring of agitator 1. milking
0..120 min.
30
Time of the set cooling start delay has to be en-
tered here, to avoid a false alarm by an agitator
that does not start.
Delay of tank monitor activation see section 8.6
Range
Def.
H90 Delay period
0..300 min. 180
Parameter level locking
Range
Def.
h98 Password protection
0 .. FFFF
0
h99 Password protection
0 .. FFFF
0
Information o password protection:
Since with the parameterization of the H-parameters the important critical alarms
are set, this level can be protected by a password.
In the delivery status of the tank monitor, the password protection is parameterized
with “O” - this means: Password protection deactivated.
For the activation of the password protection the following steps are necessary in
parameters [H98 and H99]
- enter the identical password
- quit the H-parameter level
The password request is made when re-entering the level-
code “F94A”.
ATTENTION: Please write down the password!!
Additional information on the errors see 6.5.1