7. Setting of parameters
Page 48
105466
– TW-31-E - V1.9 - 06.04.2021
7.4
Level “Extended tank monitor parameters” (H parameters)
No-load
– temperature conditions
see section 8.4
Fault
Range
Def.
H10 Milk temperature too high for too long 1
Enter “Overtemperature 1” in °C
F1
0..50,0 °C
13,0
H11 Zeitlimit für [H10]
0: deactivated
1..999: time limit overtemperature 1 in minutes
0..999 min.
600
H12 Milk temperature too high for too long 2
Enter “Overtemperature 2” in °C
F2
0..50,0 °C
16,0
H13 Zeitlimit für [H12]
0: deactivated
1..999: time limit overtemperature 2 in minutes
0..999 min.
360
H14 Milk temperature too high for too long 3
Enter “Overtemperature 3” in °C
F3
0..50,0 °C
28,0
H15 Zeitlimit für [H14]
0: deactivated
1..999: time limit overtemperature 3 in minutes
0..999 min.
300
Downtimes Power pack necessary!
H19 Max. temperature in case of power failure
Alarm activation F6 only, when the milk temper-
ature exceeds this temperature in case of a
power failure
F6
0..30 °C
7,0
H20 Max. power failure time in cooling mode
0: deactivated
1…999: time limit until alarm in minutes
F6
0..999 min.
300
Cooling time see section 8.5
H21 Minimum cooling temperature
Enter “target-cooling temperature” in °C
F21
0..50,0 °C
8,0
H22 Maximum time until cooling temperature
has been achieved [H21]
0:
deactivated
1..999: time limit until target-cooling temperature
has been achieved
0..999 min.
210
Switch to level
“Extended tank monitor parameters”
see section 7.2
H parameters
Code: F94A
Working level
Additional information on the errors see 6.5.1
General tank monitor parameter
Code: 4711
Extended tank monitor parameter
Code: F94A
Alarm configuration
Code: FFFF
Hardware configuration
Code: A384
Sensor adjustment
Code: C212
Service parameter
Code: EA03
I/O test parameter
Code: 10E5