Connections, operating elements and LEDs
Each output can switch a maximum of 500mA. To achieve
higher currents, individual outputs can be combined into
groups of 2 or 4. The maximum switching current is the total
of the individual currents: max. 1A for 2 outputs, max. 2A for 4
outputs
The outputs have thermal overload protection and are short circuit
protected.
Web-based Management can be used to activate load
monitoring, which lets the user know when there is no load
(e.g., cable break) or overload.
When dimensioning the output voltage supply, the required current
should be taken into consideration. If the selected output voltage
varies between 12V and 24V, Vcc and Vdd can also be supplied
from the same source.