Project planning with long intake lines > Ø 25 mm
Project planning for long pipe intake lines may only be carried out under use
of pipes with a diameter of 32 mm or 40 mm.
NOTICE
Observe national regulations during project planning!
The pipe intake line here refers to the pipe system between the air sampling
smoke detection system and the last T-piece (U- and double U- pipe system)
and/or the 1
st
sampling aperture (I-pipe system).
The general pipeline project planning is limited by the use of long pipe intake
lines as follows:
▪ 1 m pipe with ∅ 32 mm replaces 2 m pipe with ∅ 25 mm
▪ 1 m pipe with ∅ 40 mm replaces 3 m pipe with ∅ 25 mm
Figure 50: Example of a pipe system for project planning with long pipe intake lines
A basis pipe from which spur-shaped sampling pipes extend can be installed
for the project planning of high-bay storage shelves.
5.3.4
Summary of Contents for TITANIUS TOP-SENS
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS TOP SENS Rev a Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ...TITANUS TOP SENS Rev a Rev a 12 06 13 ...
Page 16: ......
Page 56: ......
Page 62: ...Design TITANUS TOP SENS Rev a 62 06 13 Figure 32 Pipe designs ...
Page 72: ...Design TITANUS TOP SENS Rev a 72 06 13 ...
Page 140: ...Installation TITANUS TOP SENS Rev a 140 06 13 Figure 77 Connecting the TITANUS ...
Page 148: ......
Page 204: ......
Page 206: ......
Page 210: ......
Page 216: ......
Page 226: ......
Page 240: ......
Page 246: ...TITANUS TOP SENS Rev a Glossary TS_A_Glossar en e DOC Data 04 09 ...
Page 247: ......
Page 248: ......
Page 249: ...TITANUS TOP SENS Rev a 06 13 205 ...
Page 250: ...TITANUS TOP SENS Rev a ...