Commissioning
TITANUS
TOP·SENS
®
/Rev.a
176
06/13
Adjustment Air Flow Sensor
NOTICE
To correctly adjust TITANUS
®
for the connected pipe system, the device
must have been in operation for at least 30 minutes.
▪ Adjustment can be made independent of the current air pressure (see
chapter ”Adjustment Independent of Air Pressure”). Any restrictions for
this type of adjustment see chapter design “Air Flow Monitoring”.
▪ The air flow sensor can be adjusted dependent on the current air pres-
sure (see chapter “Adjustment Dependent on the Air Pressure”). Refer to
the air pressure adjustment chart in the appendix.
To correctly evaluate the air flow sensor value, always record the type of ad-
justment in the inspection protocol.
8.1
Adjustment Types