Commissioning
TITANUS
TOP·SENS
®
/Rev.a
178
06/13
Adjustment dependent on the air pressure
Figure 105: Adjustment dependent on the air pressure of the air flow sensor of TITA-
NUS TOP·SENS
®
For the adjustment dependent on the air pressure of the air flow sensor a ba-
rometer (Recommendation: digital precision pocket barometer GPB 1300,
Greisinger electronic) and a multimeter are necessary. Follow the steps be-
low:
1. Make sure the device has been in operation for at least 30 minutes.
2. Determine the height above sea level of the mounting location of the air
sampling smoke detection system and register the value in the commis-
sioning protocol.
3. Measure the air pressure by means of the pocket barometer and the
ambient temperature by means of a temperature measuring instrument.
Register both values in the commissioning protocol.
4. Determine the adjustment value for the air flow sensor according to the
air pressure adjustment charts (refer to appendix) and register the value
in the commissioning protocol. Pay attention that the adjustment chart
corresponds to the design of the pipe system.
5. Connect the multimeter to the measuring points MP2 (+), MP3 (-) (see
fig. „Adjustment dependent on the air pressure of the air flow sensor“).
Pay attention to the polarity. Choose the "V-DC" range of the measuring
device. The standard voltage at the measuring points is 1.2 V.
8.1.2
Summary of Contents for TITANIUS TOP-SENS
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS TOP SENS Rev a Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ...TITANUS TOP SENS Rev a Rev a 12 06 13 ...
Page 16: ......
Page 56: ......
Page 62: ...Design TITANUS TOP SENS Rev a 62 06 13 Figure 32 Pipe designs ...
Page 72: ...Design TITANUS TOP SENS Rev a 72 06 13 ...
Page 140: ...Installation TITANUS TOP SENS Rev a 140 06 13 Figure 77 Connecting the TITANUS ...
Page 148: ......
Page 204: ......
Page 206: ......
Page 210: ......
Page 216: ......
Page 226: ......
Page 240: ......
Page 246: ...TITANUS TOP SENS Rev a Glossary TS_A_Glossar en e DOC Data 04 09 ...
Page 247: ......
Page 248: ......
Page 249: ...TITANUS TOP SENS Rev a 06 13 205 ...
Page 250: ...TITANUS TOP SENS Rev a ...