JC-400-005 

I56-3573-001R

This  sensor  must  be  installed  in  compliance  with  the  control  panel  system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 
installed in compliance with the National Fire Protection Association (NFPA); 
see NFPA 72.

GENERAL DESCRIPTION

Model 2951JR is an intelligent sensor that combine a state-of-the-art photoelec-
tronic sensing chamber with communications.

Two  LEDs  on  each  sensor  light  to  provide  a  local,  visible  sensor  indication. 
Remote LED annunciator capability is available as an optional accessory (Part 
No. RA400Z). The sensor will support either FlashScan™ or CLIP (Classic Loop 
Interface Protocol) SLC communication mode.

Johnson Controls panels offer different feature sets across different models. 
As a result, certain features of the 2951JR may be available on some control 
panels, but not on others. The possible features available in the 2951JR, if sup-
ported by the control unit are:

1.   The panel controls the LED operation on the sensor. Operational modes are 

RED blink, RED continuous, GREEN blink, GREEN continuous, and off.

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

When 2951JR is used in duct applications with a DNR/DNRW, testing can be 
done remotely using approved System Sensor test accessories, eliminating the 
need for a test coil.

NOTE: Only System Sensor approved accessories may be used with the 2951JR.
The  2951JR  requires  compatible  addressable  communications  to  function 
properly. Connect the 2951JR sensor to listed-compatible control panels only.

SPACING

Johnson Controls recommends spacing sensors in compliance with NFPA 72. 
In low air flow applications with smooth ceilings, space sensors 30 feet apart. 
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to NFPA 72 or the System Smoke Detector Application Guide, 
(A05-103-XX) available from Johnson Controls.

Duct  Applications:  2951JR  is  listed  for  use  in  ducts.  See  Duct  Applications 
Guide A05-1004 for details on pendant mount applications.

WIRING INSTRUCTIONS

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper  connections  will  prevent  a  system  from  responding  properly  in  the 
event of a fire.

Disconnect power from the SLC communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the wiring diagram, Figure 1.
2.   Set the desired SLC address on the sensor address switches.
3.   Install  the  sensor  into  the  sensor  base.  Push  the  sensor  into  the  base 

while turning it clockwise to secure it in place.

I56-3573-00

1R

INSTALLATION AND MAINTENANCE INSTRUCTIONS

2951JR Intelligent Photoelectric 
Smoke Sensor with Remote Test 
Capability in Duct Applications

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Standby Current: 

300µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)

Maximum Alarm Current (LED on): 

6.5 mA @ 24 VDC

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range: 

32°F to 120°F (0°C to 49°C) 2951JR, -4°F to 158°F (-20°C to 70°C) 2951JR in duct applications

Height: 

2.0˝ (51 mm) installed in B210LPJ and B501J Bases

Diameter: 

6.1˝ (155 mm) installed in B210LPJ Base; 4.1˝ (104 mm) installed in B501J Base

Weight: 

5.2 oz. (147 gm)

4.   After all sensors have been installed, apply power to the control unit and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

FIGURE 1. WIRING DIAGRAM:

3

2

1

3

2

1

+

-

-

+

+

-

REMOTE 

ANNUNCIATOR

UL

 LISTED COM

P

A

TIBLE 

CONTROL

 P

ANEL

OPTIONAL RETURN LOOP

DO NOT LOOP WIRE 

UNDER TERMINAL 1 OR 2. 

BREAK WIRE RUN TO 

PROVIDE SUPERVISION 

OF CONNECTION.

C0147-00

Note: Only System Sensor approved accessories may be used with the 2951JR.

FIGURE 2. ROTARy SLC ADDRESS SWITChES:

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0162-00

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

TAMPER-RESISTANCE

Model 2951JR includes a tamper-resistant capability that prevents its removal 
from the bracket without the use of a tool. Refer to the base manual for details 
on making use of this capability.

TESTING

Before  testing,  notify  the  proper  authorities  that  the  system  is  undergoing 
maintenance,  and  will  temporarily  be  out  of  service.  Disable  the  system  to 
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Test-
ing  methods  must  satisfy  the  Authority  Having  Jurisdiction  (AHJ).  Sensors 
offer maximum performance when tested and maintained in compliance with 
NFPA 72. The sensor can be tested in the following ways: