Delay period of alarm activation
The delay period for the alarm thresholds can be set via the switch S1 (3, 4).
As a standard the delay period for the alarm is set to 10 sec. If the smoke
level increases during operation so that the alarm threshold is reached the
delay period starts. After the delay period has been expired the signal is
transmitted if the alarm remains activated. Thus, a false alarm can be
avoided in case of short interferences (dust).
Alarm
Delay Period
switch S1
contact 3
switch S1
contact 3
0 seconds
off
off
10 seconds (Standard)
on
off
30 seconds
off
on
60 seconds
on
on
TIP
The alarm delay period should be set to 0 seconds for test purposes only.
Activating threshold for air flow monitoring
Set the activating threshold for the air flow fault via switch S1 (5, 6) on the
detector module (see figure “Detector module”) of TITANUS
®
.
level
activating threshold
Switch S1
Contact 5
Switch S1
Contact 6
I low
on
off
II
medium (standard)
off
on
III high
off
off
IV very
high
on
on
Choose the activating threshold according to chapter "Pipe Design".
6.3.1.2
6.3.1.3
Summary of Contents for TITANIUS TOP-SENS
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS TOP SENS Rev a Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ...TITANUS TOP SENS Rev a Rev a 12 06 13 ...
Page 16: ......
Page 56: ......
Page 62: ...Design TITANUS TOP SENS Rev a 62 06 13 Figure 32 Pipe designs ...
Page 72: ...Design TITANUS TOP SENS Rev a 72 06 13 ...
Page 140: ...Installation TITANUS TOP SENS Rev a 140 06 13 Figure 77 Connecting the TITANUS ...
Page 148: ......
Page 204: ......
Page 206: ......
Page 210: ......
Page 216: ......
Page 226: ......
Page 240: ......
Page 246: ...TITANUS TOP SENS Rev a Glossary TS_A_Glossar en e DOC Data 04 09 ...
Page 247: ......
Page 248: ......
Page 249: ...TITANUS TOP SENS Rev a 06 13 205 ...
Page 250: ...TITANUS TOP SENS Rev a ...