DIP-34A-03
Analog Addressable Photoelectric
Smoke Detector
INSTRUCTION MANUAL
GENERAL
DIP-34A-03 Analog Addressable Photoelectric Smoke Detector (hereinafter referred to as the DIP-34A-03 or the detector)
is to be used in a fire alarm system. It is designed to detect fires which come with appearing of smoke within closed
spaces.
The DIP-34A-03 operates under control of the S2000-KDL or S2000-KDL-2I controller which the detector is connected to
and which supplies power and communicates data with the DIP-34A-03 via the two-wire multiplex addressable polling
loop being a part of an Orion integrated security system. Up to 127 DIP-34A-03 detectors can operate under a single
S2000-KDL or S2000-KDL-2I.
The DIP-34A-03 detects smoke inside its sensing chamber by sensing light reflected by smoke particles and responds
with its state to the S2000M panel or Orion Pro software via the S2000-KDL or S2000-KDL-2I controller. Depending on
detected smoke amount these states can be Norm, Fire Prealarm or Fire Alarm.
The detector meets the requirements of Appendix “P” of Russian Regulations
СП
5.13130.2009.
In addition, the detector
can respond to the console’s request with a current condition of its sensing chamber which corresponds to its smoke or
dust level. Based on this answer, an operator of the control panel can make a decision about maintenance works or
waiting for a Fire Pre-alarm message in case of appearance of smoke at the beginning of a fire.
Electromagnetic compatibility of the detector meets the requirements of the third immunity level accordingly to Russian
standards.
The DIP-34A-03 supports DPLS_v2.xx Multiplex Addressable Polling Loop Protocol enabling monitoring addressable loop
voltage at the detector’s location. The version of DIP-34A-03 firmware is 1.01.
Operability of the detector can be periodically tested by means of a laser test tool (such as the test tool produced by the
System Sensor Company).
SPECIFICATIONS
Sensitivity
0.05 - 0.2 dB/m (1.2 %/m to 4.7 %/m)
Response Time
10 s max
Ingress Protection Rating
IP 41
Input Voltage (from an S2000-KDL(-2I))
8 ÷ 11 V dc
Current Consumption (via the loop of the S2000-KDL(-2I)) 0.5 mA max
Pre-operation Time
60 s max
Operating Temperatures
−
30 to +55°C
Storage Temperatures
−
50 to +50°C
Humidity
Up to 93% at +40°C, non-condensing
Overall Dimensions (diameter x height)
100
×
47 mm max
Weight
0.2 kg max
Average Lifetime
At least 10 years
The content of precious materials
No need to account for storage, disposal and recycling
(Clause 1.2 of Russian Standard
ГОСТ
2.608-78)
STANDARD DELIVERY
For single-piece delivery:
For group delivery:
DIP-34A-03 Detector
- 1 pc.
DIP-34A-03 Detector
- 10 pcs.
Instruction Manual
- 1 pc.
Instruction Manual
- 1 pc.
Address Sticker
- 1 pc.
Address Sticker
- 10 pcs.
Protective Cover
- 1 pc.
Protective Cover
- 10 pcs.
Unit Package
- 1 pc.
Group Package
- 1 pc.
WIRING
Figure 1 shows the connection diagram for connecting a DIP-34A-03 detector to the addressable polling loop of an
S2000-KDL or S2000-KDL-2I controller. The first terminal of the mounting base can be used to connect a cable screen.