Technical Description
TITANUS
TOP·SENS
®
/Rev.a
24
06/13
Functions
The aspiration unit in the basic device takes air samples from the protected
area via a pipe system with defined sampling points and carries them to the
sensitive detector module (see fig. „Overview air sampling smoke detection
system TITANUS
®
").
Depending on the display sensitivity of the selected detector module (levels
of 0.05 %/m, 0.01 %/m or 0.0015 %/m light obscuration can be selected),
TITANUS
TOP·SENS
®
activates the alarm when the corresponding light ob-
scuration is achieved. Four different sensitivities can be set. Three alarm
levels (alert alarm, action alarm and fire alarm) are indicated on the device
via the alarm LED and transmitted to a central fire alarm system (FAS).
Different delay periods can be set for the alarm thresholds, fault indicator
and fault transmission (see chapter Installation „Settings“).
Alarm reports are saved and the indicators have to be reset after eliminating
cause of the alarm.
By using two detector modules, TITANUS
TOP·SENS
®
2 can monitor two
areas as described above.
Via the additional input “AltSens” on the connection board of TITANUS
TOP·SENS
®
the adjusted detector modules can be set one step less sensi-
tive (e.g. the sensor modules would thus be switched from a sensitivity of 0.4
%/m to 0.8 %/m).
By changing the sensitivity of the modules, it is possible to adjust the smoke
detection to operational interferences such as
▪ increase of aerosol or dirt particles in the protected area depending on
the time of day (day/night operation).
▪ increase of aerosol or dirt particles in the protected area depending on
activity (e.g. maintenance work, welding or increase of steam, waste
gases and dust).
TITANUS
®
incorporates an intelligent signal processing system with
LOGIC·
SENS, which can be activated and deactivated with a switch at the
detector module. This fades out interferences and contributes to a safe op-
eration and avoiding false alarms.
3.1.1
Detector module
Alternative sensitivity
LOGIC·
SENS
Summary of Contents for TITANIUS TOP-SENS
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS TOP SENS Rev a Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ...TITANUS TOP SENS Rev a Rev a 12 06 13 ...
Page 16: ......
Page 56: ......
Page 62: ...Design TITANUS TOP SENS Rev a 62 06 13 Figure 32 Pipe designs ...
Page 72: ...Design TITANUS TOP SENS Rev a 72 06 13 ...
Page 140: ...Installation TITANUS TOP SENS Rev a 140 06 13 Figure 77 Connecting the TITANUS ...
Page 148: ......
Page 204: ......
Page 206: ......
Page 210: ......
Page 216: ......
Page 226: ......
Page 240: ......
Page 246: ...TITANUS TOP SENS Rev a Glossary TS_A_Glossar en e DOC Data 04 09 ...
Page 247: ......
Page 248: ......
Page 249: ...TITANUS TOP SENS Rev a 06 13 205 ...
Page 250: ...TITANUS TOP SENS Rev a ...