TITANUS
TOP·SENS
®
/Rev.a
Design
06/13
85
Double U-pipe system
1 pipe system and 2 pipe systems
Figure 42: Double U pipe system for area protection
Min. distance from TITANUS
®
– to last T-piece
4 m
Max. distance from TITANUS
®
– to last T-piece
20 m
Max. branch length
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
20 m
30 m
Max. Overall pipe length per pipe system
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
100 m
140 m
Min. distance between 2 aspiration apertures (d)
4 m
Max. distance between 2 aspiration apertures (d)
12 m
Max. number of aspiration apertures (n) per pipe system
12 pcs.
5.3.1.4
Rohrsysteme
Limit values