Installation of the pipe system
TITANUS
TOP·SENS
®
/Rev.a
160
06/13
Monitoring in forced air flow systems
(ventilation or climatic applications)
For the monitoring of ventilation and air conditioning ducts special pipe con-
figurations have to be considered.
Detection at air inlets/outlets
NOTICE
If aspiration takes place in a forced air flow system (ventilator, climatic sys-
tems), the air sampling points must be positioned in the air flow. Place the
air sampling points as shown in following figure.
Figure 91: Positioning of air sampling point, depending on air speed
Detection in bypass systems
For connection of air return refer to chapter Installation Pipe System "Air Re-
turn".