Installation of the pipe system
06/13
173
Detonation prevention devices are installed at a minimum distance of 1m
from the air sampling system into the pipe system and air return pipes. The
device is attached to these with a reducing screw-joint at the side of the pipe,
and is connected by a steel pipe to TITANUS
®
(see figure Installation of
detonation prevention device). The connection between device and screw-
joint is made with a ¾“ thread.
NOTICE
In order to have an air-tight seal between the detonation prevention device
and the steel pipe / reducing screw joint, it is essential to use either sealing
tape or joint compound.
The air flow direction plays a secondary role during installation of the de-
vice.