background image

Page 1 from 4

921

657

002_0

9

_008

BS- 657/A

The user have to read carefully the following instructions, in order to be properly informed and 
keep them for future use.

INSTALLATION

They are composed by two parts. A plastic base which is placed on the ceiling and the main 
body of the detector which fits on the plastic base with a simple rotation to the right. The 

o

detectors have a 360  visible led and a remote led driver which are light up constantly in case 
of  detection  of  fire,  till  cancelled  from  the  panel.

 

They  are  turned  off  only  when  a  reset 

command is given from the panel. The indicator led blinks every 

6

 sec indicating the normal 

function.

GENERAL

The detectors should be placed in the ceiling in visible points without side obstacles, away 
from  places  that  are  barely  ventilated  or  with  strong  air  currents  and  water  vapor.  Each 

2

detector   covers an area of 50 m  while the distance between two detectors should not be 
more than 15m. Also, they must be placed at least 50 cm away from fluorescent lamps. Cable 
diameter should be from 

0

.

to 

2

.

5mm

.

The 

BS-

6

5

7/A is a conventional smoke detector which integrates functions of optical smoke 

and heat detection. It can detect smoke and heat. The detector transitions to alarm state when 

o

the concentration of smoke reaches 0

.107

dB/m or when the temperature   reaches 57 C. 

o

Also, the detector transitions to alarm state when the temperature rises suddenly by 32 C 
regardless of the initial temperature at the beginning of the sudden rise event.

90μΑ

17

-30

V DC

IP

42

EN 54-5,EN 54-7

1

2mA (with

 

activated onboard LED)

0.

107

 dB/m 

57

o

C

ABS/PC

1

58

 

gr.

103 (

d) x 

5

5 (h) mm

1m

Α 

for

 2 

sec

A1R

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

OPERATING TEMPERATURE RANGE

RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS

TYPICAL WEIGHT
GUARANTEE

START UP POWER CONSUMPTION

OPERATION VOLTAGE

Olympia Electronics - European manufacturer

Thank you for your trust in our products  

CLASS

INDICATORS

OUTPUT

TEMPERATURE SENSITIVITY

SMOKE CONCENTRATION SENSITIVITY

STANDBY CONSUMPTION

ALARM CONSUMPTION

TECHNICAL CHARACTERISTICS

Up to

 95%

ο

-

40

 to 

7

0  C 

To panel / to external LED driver (BS-572)

Alarm LED

2 years

Optical smoke and rate-of-rise heat detector

Warranty

Warranty

P.C. 60300 P.O. Box 06 Εginio Pierias Greece

72nd km. O.N.R. Thessaloniki-Katerini

www.olympia-electronics.gr

Olympia Electronics guarantees the quality, condition and operation of the goods. The period 
of  warranty  is  specified  in  the  official  catalogue  of  Olympia  Electronics  and  also  in  the 
technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer 
does not follow the technical instructions included in official documents given by Olympia 
Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done 
by a third party, unless Olympia Electronics has fully agreed to them in writing. 

Products that 

have  been  damaged  can  be  returned  to  the  premises  of  our  company  for  repair  or 
replacement, as long as the warranty period is valid.

[email protected]

HEAD OFFICE

Olympia Electronics reserves the right to repair or to replace the returned goods and to or not 
charge the buyer depending on the reason of defection. Olympia Electronics reserves the 
right to charge or not the buyer the transportation cost.

Page 4 from 4

921

657

002_0

9

_008

1293

21

EN 54-

5:2017,

EN 54-

7:2018

DoP: 921657002_59_001

EGINIO
PIERIAS
60300 
GREECE

BS-

6

5

7

/A

Optical smoke 
and rate-of-rise heat detector

21

1293

Reviews: