TITANUS
TOP·SENS
®
/Rev.a
Installation
06/13
125
Mounting Location
Installation of air sampling smoke detection system
When choosing the mounting location, make sure that the displays are
clearly visible. Screw the air sampling smoke detection system either directly
to the wall with its bottom casing or mount it with a special support (see
chapter "Device Support").
NOTICE
Ensure that the mounting location is not within the opening range of any
doors.
Figure 67: Installation of TITANUS TOP·SENS
®
Make sure the air outlet of the system is not blocked. The distance between
the air outlet of TITANUS
®
and adjacent objects (e.g. wall) must be at least
10 cm.
The air sampling smoke detection system TITANUS
®
can be mounted with
the air sampling pipe connectors pointing upwards or downwards. If neces-
sary, turn the lid by 180°.
6.5
6.5.1
Summary of Contents for TITANIUS TOP-SENS
Page 1: ...Air sampling smoke detection system Fire Detection TITANUS TOP SENS Rev a Technical Manual ...
Page 2: ......
Page 4: ......
Page 12: ...TITANUS TOP SENS Rev a Rev a 12 06 13 ...
Page 16: ......
Page 56: ......
Page 62: ...Design TITANUS TOP SENS Rev a 62 06 13 Figure 32 Pipe designs ...
Page 72: ...Design TITANUS TOP SENS Rev a 72 06 13 ...
Page 140: ...Installation TITANUS TOP SENS Rev a 140 06 13 Figure 77 Connecting the TITANUS ...
Page 148: ......
Page 204: ......
Page 206: ......
Page 210: ......
Page 216: ......
Page 226: ......
Page 240: ......
Page 246: ...TITANUS TOP SENS Rev a Glossary TS_A_Glossar en e DOC Data 04 09 ...
Page 247: ......
Page 248: ......
Page 249: ...TITANUS TOP SENS Rev a 06 13 205 ...
Page 250: ...TITANUS TOP SENS Rev a ...