Design
TITANUS
TOP·SENS
®
/Rev.a
88
06/13
Number of aper-
tures
2
3
4
5
6
7
8
9
10
Aspiration aper-
tures
∅
in mm*)
6,0
5,0
4,4
4,0
3,6
3,4
3,2
3,0
3,0
Number of aper-
tures
11
12
13
14
15
16
17
18
Aspiration aper-
tures
∅
in mm*)
3,0
3,0
2,5
2,5
2,5
2,5
2,5
2,5
*) Press cut diameter in aspiration-reducing film sheet
U-pipe system
1 pipe system and 2 pipe systems
Figure 44: U-pipe system, e.g. for equipment protection
Min. distance from TITANUS
®
to T-piece
2 m
Max. distance from TITANUS
®
to T-piece
20 m
Max. branch length
20 m
Max. overall pipe length Ø 25 mm
60 m
Aspiration apertures
5.3.2.2
pipe systems
Limit values