Figure 38: Quadruple U-pipe system
Number of apertures
8
16
24
32
Aspiration aperture
∅
in mm (1)
A
B
C
D
Acceleration aperture
3,2
-
-
-
-
2,5
3,0
-
-
2,5 *
2,0
2,5
3,0
-
3,0 *
2,0
2,0
2,0
2,5
3,0 *
(1) Press cut diameter in aspiration-reducing film sheet
* The distance of the acceleration aperture to the last sampling aperture is entirely elective.