7
T
z
- temperatura dell’acqua in ingresso; T
p
- la temperatura dell’acqua in uscita; T
P1
- temperatura dell’aria in ingresso; T
P2
- temperatura dell’aria in uscita; P
g
- capacità di
riscaldamento; Q
w
- flusso d’acqua;
Q
p
- flusso dell’aria; Δp - caduta di pressione nello scambiatore di calore
Volcano VR2
•
Parametri T
z
/T
p
[°C]
90/70 [°C]
80/60 [°C]
70/50 [°C]
50/30 [°C]
T
p1
[°C]
Q
p
[m³/h]
P
g
[kW]
T
p2
[°C]
Q
w
[m³/h]
Δp
[kPa]
P
g
[kW]
T
p2
[°C]
Q
w
[m³/h]
Δp
[kPa]
P
g
[kW]
T
p2
[°C]
Q
w
[m³/h]
Δp
[kPa]
P
g
[kW]
T
p2
[°C]
Q
w
[m³/h]
Δp
[kPa]
0
4850
50.1
30.7
2.21
23.8
43.1
26.5
1.9
18.3
36.2
22.3
1.59
13.5
22.3
13.7
0.97
5.7
3600
41.9
34.7
1.86
17.2
36.5
30
1.6
13.3
30.5
25.3
1.34
9.8
18.8
15.6
0.82
4.2
2400
32.7
40.6
1.45
10.8
28.3
35.2
1.25
8.4
23.9
29.7
1.05
6.2
14.8
18.4
0.64
2.7
5
4850
46.7
33.7
2.07
21.1
39.9
29.5
1.76
15.9
33.1
25.3
1.45
11.4
19
16.7
0.83
4.3
3600
39.3
37.5
1.74
15.2
33.6
32.8
1.48
11.5
27.9
28.1
1.22
8.3
16.1
18.3
0.7
3.1
2400
30.6
43.1
1.36
9.6
26.2
37.6
1.16
7.3
21.8
32.1
0.96
5.3
12.6
20.7
0.55
2
10
4850
43.6
36.8
1.93
18.5
36.7
32.6
1.62
13.6
29.8
28.4
1.31
9.4
15.6
19.6
0.68
3
3600
36.6
40.4
1.62
13.4
30.9
35.6
1.36
9.9
25.2
30.9
1.11
6.8
13.2
21
0.58
2.2
2400
28.6
45.5
1.27
8.4
24.2
40
1.07
6.3
19.7
34.5
0.87
4.4
10.4
22.9
0.45
1.4
15
4850
40.4
39.8
1.79
16
33.5
35.6
1.48
11.5
26.6
31.3
1.17
7.6
12.2
22.5
0.53
1.9
3600
34
43.1
1.51
11.6
28.2
38.4
1.25
8.3
22.4
33.6
0.99
5.5
10.3
23.5
0.45
1.4
2400
26.5
48
1.18
7.3
22.1
42.5
0.98
5.3
17.6
36.9
0.77
3.5
8
25
0.35
0.9
20
4850
37.2
42.8
1.65
13.7
30.3
38.6
1.34
9.5
23.3
34.3
1.02
5.9
8.4
25.2
0.37
1
3600
31.3
45.9
1.39
10
25.5
41.1
1.13
6.9
19.7
36.3
0.86
4.3
7
25.8
0.31
0.7
2400
24.5
50.4
1.09
6.3
20
44.8
0.88
4.4
15.5
39.2
0.68
2.8
5.3
26.6
0.23
0.4
T
z
- temperatura dell’acqua in ingresso; T
p
- la temperatura dell’acqua in uscita; T
P1
- temperatura dell’aria in ingresso; T
P2
- temperatura dell’aria in uscita; P
g
- capacità di
riscaldamento; Q
w
- flusso d’acqua;
Q
p
- flusso dell’aria; Δp - caduta di pressione nello scambiatore di calore
Volcano VR3
•
Parametri T
z
/T
p
[°C]
90/70 [°C]
80/60 [°C]
70/50 [°C]
50/30 [°C]
T
p1
[°C]
Q
p
[m³/h]
P
g
[kW]
T
p2
[°C]
Q
w
[m³/h]
Δp
[kPa]
P
g
[kW]
T
p2
[°C]
Q
w
[m³/h]
Δp
[kPa]
P
g
[kW]
T
p2
[°C]
Q
w
[m³/h]
Δp
[kPa]
P
g
[kW]
T
p2
[°C]
Q
w
[m³/h]
Δp
[kPa]
0
5700
75.1
39
3.31
32.6
64.5
33.8
2.85
25.1
54.3
28.4
2.39
18.4
33.6
17.6
1.46
7.8
4100
60.6
44.1
2.69
22
52.5
38.2
2.32
17
44.3
32.2
1.95
12.5
27.5
20
1.2
5.4
3000
49.5
49.2
2.19
15
42.9
42.7
1.89
11.6
36.3
36.1
1.59
8.6
22.6
22.5
0.98
3.7
5
5700
69.9
41.6
3.1
28.9
59.8
36.3
2.64
21.7
49.6
31
2.18
15.5
28.7
20
1.25
5.8
4100
56.8
46.3
2.52
19.5
48.7
40.4
2.15
14.8
40.5
34.4
1.78
10.6
23.5
22.1
1.02
4
3000
46.4
51.1
2.06
13.3
39.8
44.6
1.76
10.1
33.1
37.9
1.46
7.3
19.3
24.2
0.84
2.8
10
5700
65.2
44.1
2.89
25.3
55
38.8
2.43
18.6
44.8
33.4
1.97
12.8
23.7
22.4
1.03
4.1
4100
53
48.6
2.35
17.1
44.9
42.6
1.98
12.7
36.6
36.6
1.61
8.8
19.4
24.1
0.84
2.8
3000
43.3
53.1
1.92
11.7
36.7
46.5
1.62
8.7
30
39.8
1.32
6.1
15.9
25.8
0.69
2
15
5700
60.4
46.6
2.68
21.9
50.2
41.3
2.22
15.7
40
35.9
1.76
10.3
18.4
24.6
0.8
2.6
4100
49.2
50.8
2.18
14.9
41
44.8
1.81
10.7
32.7
38.8
1.44
7.1
15.1
26
0.66
1.8
3000
40.2
55
1.78
10.2
33.6
48.4
1.48
7.4
26.8
41.6
1.18
4.9
12.4
27.3
0.54
1.2
20
5700
55.6
49.1
2.47
18.8
45.4
43.8
2
13
35
38.3
15.4
8.1
12.8
26.7
0.56
1.3
4100
45.3
53
2.01
12.8
37.1
47
1.64
8.9
28.7
40.9
1.26
5.6
10.4
27.5
0.45
0.9
3000
37.1
56.9
1.64
8.8
30.4
50.2
1.34
6.1
23.6
43.4
1.04
3.9
8.3
28.2
0.36
0.6
8
VOLCANO
VR Mini
VOLCANO
VR1
VOLCANO
VR2
VOLCANO
VR3
VOLCANO
VR-D
Parametro
Unità di misura
VOLCANO
VR Mini
VOLCANO
VR1
VOLCANO
VR2
VOLCANO
VR3
VOLCANO
VR-D
Numero file del riscaldatore
2
1
2
3
---
Massima portata d’aria
m³/h
2100
5300
4850
5700
6500
Campo di potenza termica
kW
3-20
5-30
8-50
13-75
-
Temperatura massima del fattore riscaldante
°C
130
-
Pressione massima d’esercizio
MPa
1.6
-
Massimo campo orizzontale d’aria
m
14
23
22
25
28
Massimo campo verticale d’aria
m
8
12
11
12
15
Capacità idrica
dm³
1.12
1.25
2.16
3.1
-
Diametro dei tubi di giunzione
"
3/4
-
Peso del dispositivo (acqua esclusa)
kg
17.5
27.5
29
31
22
Tensione di alimentazione
V/Hz
1 ~ 230/50
Potenza motore AC
kW
0.115
0.28
0.41
Corrente nominale motore AC
A
0.53
1.3
1.7
Giri motore AC
rpm
1450
1380
IP motore AC
---
54
Potenza motore EC
kW
0.095
0.25
0.37
Corrente nominale motore EC
A
0.51
1.3
1.7
Giri motore EC
rpm
1450
1430
1400
IP motore EC
---
44
NOTA
I dati relativi ai parametri di lavoro di VOLCANO con il fluido di riscaldamento a una temperatura differente possono essere forniti su richiesta.
207