VI.17 Repeater (see section VII.3.8 for configuration)
You must have a repeater if you want to connect:
• More than one unit on the same display (maximum 6)
• A remote control at more than 100 metres
In this case you can move the remote control system up to 1 km away. Use a shielded twisted 2-pair cable of BELDEN
8723 type or equivalent to connect the repeater to the control housing. Use another cable to supply the repeater (230 V
single phase).
Connect the wires as follows:
• B of the repeater to terminal B of the VORT NRG EC unit (wire of the shielded cable as shown in the diagram below)
• A of the repeater to terminal A of the VORT NRG EC unit (wire of the shielded cable as shown in the diagram below)
• N of the repeater to terminal N of the VORT NRG EC unit (shielding of the shielded cable as shown in the diagram below)
• The remote control is connected as shown below through the RJ12 port
• 230 V / 50 Hz single-phase supply
VII SETTINGS
VII.1 / Control (on CORRIGO or remote control)
The monitor has four rows of 20 characters. It is back-lit. This lighting is not permanent but activates when a key is
pressed. The lighting switches off after a period of inactivity.
There are two LEDs on the front panel:
%
Alarm LED represented by the bell symbol.
!
Write LED represented by the pencil symbol.
Rapid blinking = possible to change the value
Slow blinking = a password needs to be entered to change the value
The
Up
,
Down
,
Left
and
Right
arrow keys are used to navigate inside the menus.
The
Up
and
Down
arrow keys are also used to increase or decrease the value of a parameter when it is accessible,
whereas the
Left
and
Right
keys are also used to navigate within the same parameter.
The
OK
key is used to enter the value and confirm a selection, and the
C
key is used to cancel.
The
Alarm
key (red) is used to access the fault list.
The left arrow is also used to exit the alarm menu to return to the main menu
The cursors show you the possible movements and on which arrows to press.
%
!
ENGLISH
maximum 6 control units
ALARM
RE
PE
AT
ER
ED
-T
O
UC
H
100 metres
M
AS
TE
R
BANE
port1
Arrows
Cursor
Option of going up
Option of going down
Analogue input:
23
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...