• Move the cursor to the cons. menu as described in section VII.2.
• Once in this menu, press the OK key.
• Enter the desired value. The outdoor temperature values are not
changeable. If you increase or decrease a value, all the others
should be increased by the same value to comply with this air
relationship principle.
• Validate by pressing the OK key to go to the next field.
• Once all the values are updated, press on the left arrow to return
to the welcome screen.
VII.3.5 Unit start/stop or forced LS/HS start by means of the CORRIGO or the remote control
You can stop
(6) (stop)
the unit with the CORRIGO control or do a forced LS
(6) (manual speed 1/2)
or HS
(6) (manual
speed 1/1) start
. As standard, the unit operates in automatic mode at all hours
(6) (auto)
Move the cursor to the menu below as described in section VII.2.
Once in this menu, press OK (AUTO = start by clock)
(Stop = stop the unit)
(manual speed 1/2 = MFPV)
(manual speed 1/ = MFGV)
• Enter the desired mode.
• Validate by pressing the OK key to go to the next field.
• Once all the modes are updated, press on the left arrow to return to the welcome screen.
An alarm appears from the time that you are not in Auto mode. The manual Speed 1/1 and manual speed 1/2
modes should be used only for commissioning and repairs. Any setting would cause the unit to malfunction.
VII.3.6 Special parameter settings (control type modification and NIGHT COOLING modification
These parameter settings require access to the Configuration menu. For this you should get the “Service” level access
rights. Follow the procedure set out below.
Enter the code
2222
with the help of the arrow arrow keys and then validate with the OK key. Press twice on left arrow to
access the menus. In case of an operating error, press twice on the C key and restart the operation.
Once this step is completed, you will get access to the configuration menu where you will be able to modify the type of
control
(NOTE: if you want to control the unit based on room temperature, selected the “Return air” control mode.
All other choices will make the unit malfunction)
and the speed of the fan in % during the night cooling period.
Words written normally = view only /
Words in bold underlined
= Modification possible with password 3333. = not used
or not accessible.
ENGLISH
Outdoor comp. set-point
-20.0° =
25.0°
-15.0° =
24.0°
-10.0° =
23.0°
0.0° =
22.0°
5.0° =
20.0°
10.0° =
18°C
15.0° =
18°C
!
Operating mode
Auto
MODE OF REGULATION
Year:month:day
Time
System: start or stop
SP: T°C set point Act.: T°C current
. . .
Access rights
Enter
. . .
Enter password of the
desired authorisation level: ****
Current lev.: None
29
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...