ENGLISH
VI.4.2 Control terminal connection
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Control terminal
(on lower DIN rail)
Name
Terminals
Connection
RMS
1
DO3*
To be connected to terminals 1 and 2 of the motorised supply air damper
(GMA 121.1E)
RMR
2
DO4*
To be connected to terminals 1 and 2 of the motorised return air damper
(GMA 121.1E)
AL
3
DO5*
To be connected to the terminals of a remote alarm indicator (2 A 24 VAC
MAX)
DBE (INFINITE and EH only)
4
DO6*
To be connected to the terminals of the defrost coil’s static switch
(detachable) (see section VI.16)
NC (night cooling) (LOBBY)
2
DO7*
24 V output available if the VORT NRG unit is associated with the LOBBY
option for opening the dampers during the night cooling period. (see section
VI.9)
DX
2
DO7*
24 V output available for starting a direct expansion module (should be
specified in the order) (see section VI.13)
ADP
5
6
To be connected to the NC contact of the remote firefighter’s stop button.
As its name suggests, this contact should be used only in a firefighter’s stop
function since it directly stops the system and shunts all the safeties.
REPEATER
7
8
B-A-N*
To be connected on the repeater if you would like to shift the remote control
more than 10 m away (see section VI.17)
MF HS
9-10
To be connected to the terminals of a NO contact provided for high-speed
forced operation
MF LS
11-12
To be connected to the terminals of a NO contact provided for low-speed
forced operation
AR EST
13-14
To be connected to the terminals of a NO contact provided for forced
external stop (note: if contact closed, unit is at stop)
* direct connection to CORRIGO
15
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...