VI.6 Connection of pressure transmitters for MAC2 / LOBBY / QUATTRO
The pressure transmitters are factory-wired.
VI.7 Connection of CO
2
transmitter for DIVA / QUATTRO
The CO2 transmitter is factory-wired
VI.8 Bypass
This function is automatically controlled using the CORRIGO regulator’s programming and the probes installed as
standard in our VORT NRG EC units.
In winter (FREE HEATING):
When heat is required, the bypass closes to recover maximum calories through the plate
exchanger. If this recovery is not adequate to reach the temperature set-point, the water coil valve (if available) will open
or the electric coil (if available) will start.
In summer (FREE COOLING):
The bypass closes when the outside temperature is higher than the inside temperature
to prevent the outside heat from entering directly. If the outside temperature is lower than the inside temperature, the
bypass opens to get the cool outside air.
On the VORT NRG 6000-8000 models, the single servomotor is wired in the same manner as the small shutter.
ENGLISH
BR
O
W
N
W
HI
TE
G
RE
EN
BR
O
W
N
W
HI
TE
G
RE
EN
SUPPLY AIR
RETURN AIR
LOBBY / MAC2 AND QUATTRO EC
PRESSURE TRANSMITTER
BR
O
W
N
W
HI
TE
G
RE
EN
Bypass servomotor recovery
unit side
SMALL SHUTTER
NRG EC terminal
Bypass servomotor recovery
unit front
LARGE SHUTTER
19
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...