VI.9 NIGHT COOLING
This function is used during summer to cool buildings at night by using cool outdoor air, thus reducing the cooling power to be delivered
during the day. The NIGHT COOLING function works only between midnight and 7 a.m..
During the Night Cooling period, the heating and cooling outlets are blocked. The bypass is also open to prevent air from
travelling through the exchanger. At the end of a NIGHT COOLING period, the heating is blocked for 60 minutes.
Operating conditions:
• The outdoor temperature was greater than 22°C during the day.
• The clocks are set either to LS or to stop between midnight and 7 a.m..
• The outdoor temperature is less than 18°C during the NIGHT COOLING period.
• The outdoor temperature is greater than 10°C during the NIGHT COOLING period.
• The room temperature is greater than 18°C.
During the NIGHT COOLING period, the fan runs at 85% capacity. This speed can be adjusted. See section VII.3.7
For the LOBBY version, a maximum 24 V 2A output is provided between the DO7 and 2 terminals to force the opening
of the dampers during the Night Cooling period.
VI.10 Automatic defrost
This function is automatically controlled using the CORRIGO regulator’s programming and the probes installed as
standard in our double-flow VORT NRG EC units. Defrosting starts with the opening of the bypass (defrost temperature,
SDG, less
than 5°C). If the bypass function is not adequate to defrost the exchanger (normally if the outside temperature is less than
-10°C), the new air fan modulates its airflow until it stops, and then restarts as soon as the defrost temperature probe
exceeds 5°C.
For the INFINITE and EH versions:
a defrost coil is installed on the new air duct, to minimise the risk of frost with the
bypass closed. The maximum efficiency of the system is thus maintained.
VI.11 Hot water and cold water coil (the valve must be connected in the OFF position)
On the
VORT PREMIUM BC
and
VORT INFINITE BC
versions, the hot water coil is already installed in the unit. The anti-
frost thermostat is connected. However, you should wire the 3-way valve.
For all other versions, also connect the THA (anti-frost thermostat) and shift the supply air probe after the battery
Connect the 3-way valve’s servomotor as follows:
Hot coil:
Terminal
20
of the VORT NRG EC unit to the +24 V (G) of the valve’s servomotor
Terminal
21
of the VORT NRG EC unit to the +0 V (G0) of the valve’s servomotor
Terminal
22
of the VORT NRG EC unit to the +10 V (Y) of the valve’s servomotor
Connect the NC contact (C and 2) of the
THA
(anti-frost thermostat) to 18 and 19
Cold coil:
Terminal
26
of the VORT NRG EC unit to the +24 V (G) of the valve’s servomotor
Terminal
27
of the VORT NRG EC unit to the +0 V (G0) of the valve’s servomotor
Terminal
28
of the VORT NRG EC unit to the +10 V (Y) of the valve’s servomotor
Connect the NC contact (C and 2) of the
THA
(anti-frost thermostat) to 18 and 19
VI.12 Changeover coil (EC FIRST versions only) (the valve
must be connected in the OFF position)
A changeover coil can be installed on the
VORT NRG EC FIRST version.
In
this case you will not be able to add another hot water or cold water coil. You should connect the 3-way valve, the
changeover handle and the THA (anti-frost thermostat), and shift the supply air
probe after the coil
Connect the appliance as described below:
Red wire of the handle (CO) to Y of the valve’s servomotor
Terminal
20
of the NRG EC unit to the +24 V (G) of the valve’s servomotor
Terminal
21
of the NRG EC unit to the +0 V (G0) of the valve’s servomotor
Terminal
22
of the NRG EC unit to the brown wire of the handle at the hot signal
Terminal
28
of the NRG EC unit to the black wire of the handle at the cold signal
Connect the NC contact (C and 2) of the
THA
(anti-frost thermostat) to 18 and 19
ENGLISH
A
AB
B
COIL
A
AB
B
COIL
20
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...