Instructions Prima Klima EN 
PK250-XLE 

 
Safety Information 

This machinery must not be put into operation until prior to reading mounting 

instructions 

and 

safety  information.  All  fans  are  intended  for  transportation  of  air 

in 

air  handling  systems.  If 

installed 

in no heated rooms, the fan casing has to be insulated in order to avoid condensation

They are meant to be used after building them into machines or duct systems or after contact 

protection grid have been 

installed. 

Fans with duct connections must be connected to ducts on 

both  sides  (inlet/outlet).  When  there  is  a  risk  of  water  entering  the  motor,  via  the  ducts, 

external protection is required. No moving parts shall be accessible after installation. The fans 

are not to be used in hazardous environments or connected to flue ducts. The fans must not be 

installed 

outdoors 

(with 

exception of roof fans and fans with, for this purpose: corresponding IP 

class).  If  the  fans  are  installed  without  insulation  in  non-heated  areas  there  is  a  risk  of 

condensation. Safety accessories (i

.

e. motor protection, safety grille) may not be dismounted, 

short cut or disconnected.  

CAUTION!

 Before servicing or maintenance, switch off power, (all-

pole circuit breaker), and make sure the impeller has come a standstill.

 CAUTION!

 The fans 

can  have  sharp  edges  and  corners  which  may  cause 

injuries.

 

CAUTION!

  Be  careful  when 

opening  the  fans  service-hatches  (swing-out),  the  fan  and  motor  assembled  on  the  hatch  is 

relatively heavy. 

 
Transportation and Storage 

All fans are packaged at the factory to withstand normal transport handling. When handling the 

goods 

use 

suitable lifting equipment in order to avoid damage to fans and personnel. Do not lift 

the fans by the connecting cable, connection box, impeller or inlet cone. Avoid blows and 

shock 

loads. Store the fans in a dry place protected from weather and dirt until final installation. 

 

 

Operation 

 

Before initial operation, check the following: 

- Electrical connection has been properly completed. 

- Protective conductor has been connected

- Motor protection installed

- Safety devices in place (protection grid) 

- Leftover 

installation 

materials and foreign materials have been removed from the casing. 

 

When putting into operation, check the following: 

- Connection data corresponds to 

the 

specifications on 

the 

nameplate

Maximum v6%, 

-10%, according to IEC 38

Rated current must not be exceeded with more than 5% at rated 

voltage. 

CAUTION!

  When  speed  regulating  by  reducing  the  voltage  the  motor  current  may 

exceed the rated current at a lower voltage. In this case the motor windings are protected by 

the thermal contact. The minimum static fall of pressure 

must 

observe

.

  

- The direction of rotation should correspond to direction of rotation arrow 

- Smoothness of motor operation, (no abnormal noises) 

- Fans must only be operated by a person that has sustainable knowledge or education within 

this field or handling must be carried out with the supervision of such person. 