VI.4 Electric board’s terminal
VI.4.1 Power terminal connection
ENGLISH
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
33
34
35
36
37
32
38
39
40
41
42
43
44
45
46
Power terminal and accessories
for fan operations
(on upper DIN rail)
29
30
31
33
34
35
36
37
32
38
39
40
41
42
43
44
45
46
Power terminal and
accessories for fan operation
(on upper DIN rail).
Control terminal
(on lower DIN rail)
Name
Terminals
Connection
DEP S
29-30
To be connected to terminals 1 and 3 of the
DEP
airflow control pressure switch on supply air fan
set at 30Pa (note: the safety of the airflow shall be
managed by the pressure transmitter if using the
LOBBY, QUATTRO or MAC2 option. In this case do
not connect anything to these terminals).
SUPPLY AND
RETURN AIR MOTOR
31-32-33-
34-35-36-
40-41
According to VORT NRG EC size (see section VI.5)
DEP S
38-39
To be connected to terminals 1 and 3 of the
DEP
airflow control pressure switch on return air fan set
at 30Pa (note: the safety of the airflow shall be
managed by the pressure transmitter if using the
LOBBY, QUATTRO or MAC2 option. In this case do
not connect anything to these terminals).
BE regulator
(PREMIUM and
INFINITE BE only)
42-43
For
VORT NRG EC PREMIUM BE
and
VORT
NRG EC INFINITE BE
only, connect to terminals 1
and 2 of the
BE regulator
(see section VI.15)
DEP FS
44-45
To be connected to terminals 1 and 3 of the
DEP
fouling pressure switch of the supply air filter (set
at 200 Pa)
THS (PREMIUM and
INFINITE BE only)
37-46
For
VORT NRG EC PREMIUM BE
and
VORT NRG
EC INFINITE BE
only, connect to terminals C and 2 of
the electric coil’s safety thermostat (see section VI.15)
14
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...