Configuration
The communication parameters for the Modbus line are the most important thing to configure first. As described earlier,
these parameters must be identical in both the master unit and slave units, since they define the structure of messages
and the transmission speed.
The default configuration values of a Corrigo E controller are shown in the figure below.
Corrigo E is set to Slave 1 address by default. If more devices are added, a new address can be set for each device using
the Corrigo E display or E tool.
Transmission mode
Corrigo E uses the RTU transmission mode; not to be confused with the ASCII mode. The settings for the transmission
mode must be the same in the master unit and the slave units, since Modbus/RTU cannot understand Modbus/ASCII
messages. The Word length configuration parameter is always 8 for Modbus/RTU.
Writing values
To override the Corrigo E output values, set the output to manual mode using a Modbus signal. Then set the ..._ManSet
signal to the desired layer. These signals are listed in Chapter 5: Holding Registers Remember that only values with a
default value are adjustable. The are described in the chapters Coil Status Register and Holding Register.
Reading values
An effective way to read values is to display multiple variables simultaneously. For example, to read all analogue outputs,
set the Modbus query to the values shown in the figure below. The first analogue output variable starts at address 54
(QAnaOut.AQ1). To read address 54 to 58, set the length to 5. The Modbus answer will then communicate the 5 values
in a single message, making the communication more effective.
ENGLISH
47
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...