VII.3.8.f BACNET IP type B communication
To activate BACNET and change the parameters (fixed IP, name of controller…), download the appropriate E-tool software
or the lightweight WEB configuration software from: http://www.regin.se (download tab)
You will find the complete WEB variables list at: http://www.regin.se.
VIII REPAIR
VIII.1 Various examples of faults
The Regulation of the VORT NRG EC units is equipped with alarms. When the red LED blinks, press on the alarm button
(red) to display the fault.
Faults are classified into class A, B or C (see details below)
Type of fault:
A: The fault stops the ventilation system. The device does not start until the problem is solved and the fault is eliminated.
B: The fault does not stop the ventilation system. To clear the alarm, the fault must be eliminated. It remains in the the log
but does not prevent the system from functioning.
C: The fault does not stop the ventilation system and disappears automatically as soon as the problem is resolved.
ENGLISH
Description of fault
Cause
CORRIGO screen not lighting
Power supply to unit is incorrect (P/B LED of CORRIGO off)
- To light screen, press on a key (back-lighting).
The fan(s) is/are not working
The clocks are at 0 or you have no external start order
Remote control is not working or
is giving wrong values
Remote control wire not original (wire changed, shortened or extended)
Repeater wrongly connected
32
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...