XII HOLDING REGISTER
ENGLISH
Signal name
Ex
o t
yp
e
M
od
bu
s a
dd
re
ss
De
fau
lt v
alu
e
Function
Description
VentSetting.Cor_Curve1_Y 1
R 10 25°C
Supply, extract and
room temperature
Supply setpoint for -20°C
outdoor T°C
V entSetting. Cor_Curve 1 _Y 2
R 11 24°C
Supply, extract and
room temperature
Supply setpoint for -15°C
outdoor T°C
V entSetting. Cor_Curve 1 _Y 3
R 12 23°C
Supply, extract and
room temperature
Supply setpoint for -10°C
outdoor T°C
VentSetting.Cor_Curve1_Y 4
R 13 23°C
Supply, extract and
room temperature
Supply setpoint for -5°C
outdoor T°C
VentSetting.Cor_Curve1_Y 5
R 14 22°C
Supply, extract and
room temperature
Supply setpoint for -0°C
outdoor T°C
VentSetting.Cor_Curve1_Y 6
R 15 20°C
Supply, extract and
room temperature
Supply setpoint for +5°C
outdoor T°C
V entSetting. Cor_Curve 1 _Y 7
R 16 18°C
Supply, extract and
room temperature
Supply setpoint for +10°C
outdoor T°C
VentSetting.Cor_Curve1_Y 8
R 17 18°C
Supply, extract and
room temperature
Supply setpoint for +15°C
outdoor T°C
VentSetting.Cor_ExhaustSetpoint
R 18 21°C
Supply, extract and
room temperature
Recovery reference value (if
configured in recovery mode)
VentSetting.Cor_SAFFullspeedOutput
R 424 70%
SAF/EAF pressure and
flow
GV supply speed setting
VentSetting.Cor_SAFHalfspeedOutput
R 425 50%
SAF/EAF pressure and
flow
PV supply speed setting
VentSetting.Cor_EAFFullspeedOutput
R 426 70%
SAF/EAF pressure and
flow
GV recovery speed setting
V entSetting. Cor_EAFHalfspeedOutput R 427 50%
SAF/EAF pressure and
flow
PV recovery speed setting
VentSetting.Cor_SAFHalfspeedPressure R 25 180 Pa
SAF/EAF pressure and
flow
Supply pressure setting
(LOBBY EC)
VentSetting.Cor_EAFHalfspeedPressure R 27 180 Pa
SAF/EAF pressure and
flow
Recovery pressure setting
(LOBBY EC)
VentSetting.Cor_SAFFullspeedAirFlow
R 28 2000m3/h SAF/EAF pressure and
flow
GV supply speed setting
(MAC2 QUATTRO EC)
VentSetting.Cor_SAFHalfspeedAirFlow R 29 1000m3/h SAF/EAF pressure and
flow
PV supply speed setting
(MAC2 QUATTRO EC)
VentSetting.Cor_EAFFullspeedAirFlow
R 30 2000m3/h SAF/EAF pressure and
flow
GV recovery speed setting
(MAC2 QUATTRO EC)
V entSetting. Cor_EAFHalfspeedAirFlow R 31 1000m3/h SAF/EAF pressure and
flow
PV recovery speed setting
(MAC2 QUATTRO EC)
V entSetting. Cor_CO2 setpoint
R 32 1000pp
m
CO2
CO2 reference value setting
(DIVA QUATTRO EC)
49
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...