VII.3.8 Modification of system parameters
VII.3.8.a Access to system level
These parameter settings require access to the Configuration menu. For this you should get the “System” level access
rights. Follow the procedure set out below.
Enter the code
1111
with the help of the arrow arrow keys and then validate with the OK key. Press twice on left arrow to
access the menus. In case of an operating error, press twice on the C key and restart the operation.
Once this step is completed, you will have access to the configuration menu where you will be able to enable the
MODBUS and modify the PLA and ELA addresses
VII.3.8.b Repeaters and EXO communication [
(6)
section VII.6] (
password 1111 required
)
Access: Configuration/System
An instruction manual is delivered with each repeater. If you have several Corrigos connected to the same remote control
(up to 6 CORRIGOS), you must change the PLA/ELA on each CORRIGO address. In this case, it will have a different
address on each CORRIGO, and you need to enter the same address in the repeater. Follow the manual provided to set
the addresses
in the CORRIGO.
VII.3.8.c MODBUS communication via RS485 (CORRIGO standard) [
(1) (2) (3) (4) (5)
section VII.6] (
password
1111 required
)
Access: Configuration/Communication
You need to activate MODBUS communication. You can change the address, parity, speed, etc. You will find the complete
MODBUS variables list at the end of this document.
Select list ex 3.3 or higher depending your CORRIGO version
VII.3.8.d LON communication (in case of CORRIGO LON only) section VII.6
Activate LON communication as described below
In the menu Configuration/Communication/Function port 2 menu = activate port 2 in the extension unit.
Press the right arrow and activate it it in the CORRIGO E28 LON
To make a service PIN, press the back button on the controller
You will find the complete LON variables list at: http://www.regin.se.
Select list ex 3.3 or higher depending your CORRIGO version
VII.3.8.e WEB communication
It is possible to communicate via the WEB using TCP/IP. In this case the controller is delivered with the Internet page
loaded and the controller is set to DHCP.
To set this parameter (fixed IP, name of controller…), download the appropriate E-tool software or the lightweight WEB
configuration
software from: http://www.regin.se (download tab)
ENGLISH
MODE OF REGULATION
Year:month:day
Time
System:start oper. or stop
SP: T°C set point Act.: T°C current
. . .
Access rights
Enter
. . .
Enter password of the
desired authorisation level: ****
Current lev.: None
31
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...