XI INPUT REGISTER
ENGLISH
Signal name
E
x
o
t
y
p
e
M
o
d
b
u
s
a
d
d
re
s
s
D
e
fa
u
lt
v
a
lu
e
Function
Description
VentActual. Cor_RunMode
X
3
Actual/Setpoint
0=stopped
1=starting up
2= reduced speed starting
3= full speed starting
4= normal speed starting
5= running
6= heating restart
7= cooling restart
8= C02 running
9= night cooling
10= full speed mode
11= stopping
VentActual. Cor_OutDoorAirTemp
R
1
Supply, Extraction,
ambient
Outdoor temperature
V entActual. Cor_SAFRunTime
R
4
Actual/Setpoint
Blowing fan running time
VentActual. Cor_EAFRunTime
R
5
Actual/Setpoint
Recovery fan running time
V entActual. Cor_SupplyAirTemp
R
7
Supply, Extraction,
ambient
Supply temperature
V entActual. Cor_ExhaustAirTemp
R
9
Supply, Extraction,
ambient
Extraction temperature
VentActual. Cor_SAFPressure
R
13
SAF/EAF pressure and
flow
New air pressure (LOBBY EC)
VentActual. Cor_EAFPressure
R
14
SAF/EAF pressure and
flow
Recovery air pressure (LOBBY EC)
VentActual. Cor_SAFAirFlow
R
15
SAF/EAF pressure and
flow
New air pressure (MAC2
QUATTRO EC)
VentActual. Cor_EAFAirFlow
R
16
SAF/EAF pressure and
flow
Recovery air pressure (MAC2
QUATTRO EC)
V entActual. Cor_CO2 Sensor
R
17
CO2
CO2(ppm)
VentActual. Cor_DeIcingTemp
R
21
Emission, Defrost
Defrost temperature
VentActual. Cor_ExtraSensor
R
25
Additional probe
Defrost temperature (INFINITE)
QAnaOut.AQl
R
54
Analogue output
0-10 V Heating
QAnaOut.AQ2
R
55
Analogue output
0-10 V Exchanger
QAnaOut.AQ3
R
56
Analogue output
0-10 V Exchanger
QAnaOut.AQ4
R
57
Analogue output
0-10 V Supply
QAnaOut.AQ5
R
58
Analogue output
0-10V Recovery
48
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...