ENGLISH
Display
Description
Type
Time
Cause
Elec. coil
overheat
The electric coil is
overheating
A
0 sec
Safety thermostat triggered.
Battery weak
Internal battery error
A
0 sec
CORRIGO’s internal battery is not working
Quickly change the battery so as not to lose the schedule.
See section VIII.2
High supply air
temperature
The supply air
temperature exceeded
the temperature limit
B
10 sec
The supply air temperature exceeded 50°C
The temperature set-point is too high
AN vent. fault
Supply air fan not
working
A
30 sec
(120sec for
LOBBY
MAC2
QUATTRO
EC)
The pressure switch is wrongly connected (the pressure switch
should be set to 30Pa).
Motor not working
The pressure read by the transmitter is less than 30Pa. (CARMA
LOBBY, MAC2 and QUATTRO) (contact Vortice)
The motor’s thermal cut-out has triggered.
AR vent. fault
Return air fan not
working
A
30 sec
(120sec for
LOBBY
MAC2
QUATTRO)
The pressure switch is wrongly connected (the pressure switch
should be set to 30Pa).
Motor not working
The pressure read by the transmitter is less than 30Pa. (LOBBY,
MAC2 and QUATTRO) (contact Vortice)
The motor’s thermal cut-out has triggered.
External
antifreeze
protection
Antifreeze protection
triggered
C
120 sec
Thermostat not set to 5°C
Thermostat not working
Circulation pump not working
The 3-way valve is wrongly wired, wrongly connected
hydraulically or is not working
Filter fouling
Filter fouling pressure
switch
C
0 sec
The pressure switch is wrongly connected (the pressure switch is
set to 200Pa). The filter is fouled.
VAS pressure
error
Difference of more
than 50Pa between
the set-point and the
pressure reading
C
30 min
The network does not match the fan selected or the pressure set-
point.
(LOBBY
VAR pressure
error
Difference of more
than 50Pa between
the set-point and the
pressure reading
C
30 min
The network does not match the fan selected or the pressure set-
point.
(LOBBY)
33
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...