VII.3.3 Modification of speed / pressure / airflow in LS and HS (password required)
VII.3.3.a
VORT NRG EC
and
DIVA (5)
section VII.2
You can change the rotation speeds of your unit to LS (reduced speed) and HS (normal speed) for each fan in order to
set your own customised airflows. To set your initial HS airflow, force the system into normal speed with the “Forced HS”
terminals (bridge between terminals 9 and 10). To set your initial LS airflow, force the system into reduced speed with the
“Forced LS”
terminals (bridge between terminals 11 and 12).
Move the cursor to
the AS or AR manual vent. frequency control menu
as described in chapter VII.2.
Once in this menu, press the OK key (1/1 = GV)
(1/2 = PV)
• Enter the desired value using the graphs in the appendix
at the end of the instructions.
• Validate by pressing the OK key to go to the next field.
• Once all the values are updated, press on the left arrow
to return to the welcome screen.
VII.3.3.b VORT NRG EC LOBBY (5) section VII.2
You can change the constant pressure of your unit for each fan to set your own customised airflows. To set your initial
HS airflow, force the system into normal speed with the “Forced LS”
terminals (bridge between terminals 11 and 12).
Move the cursor to the VAS pressure control menu as described in section VII.2.
Once in this menu, press the OK key
• Enter the desired value.
• Validate by pressing the OK key to go to the next field.
• Once all the values are updated, press on the left arrow
to return to the welcome screen.
VII.3.3.c VORT NRG EC MAC2 and QUATTRO
(5)
section VII.2
You can change the constant speeds of your unit to LS (reduced speed) and HS (normal speed) for each fan.
Move the cursor to the VAS airflow control menu as described in section VII.2.
Once in this menu, press the OK key (1/1 = GV)
(1/2 = PV)
• Enter the desired value.
• Validate by pressing the OK key to go to the next field.
• Once all the values are updated, press on the left arrow
to return to the welcome screen.
VII.3.4 Temperature set-point modification (password required) (7) section VII.2
The control is based on the supply air temperature control with outdoor compensation. Normally, the supply air
temperature set-point moves according to the outdoor temperature. (See graph below).
If you need to modify this data, follow the procedure described below:
ENGLISH
Frequency control
AS or AR manual ventilation
Output 1/1:
70%
Output 1/2:
50%
...
VAS or VAR pressure control system
Set point 1/1: not used
Set point 1/2:
180 Pa
...
†
VAS or VAR airflow control system
Set point 1/1:
5000 m3/h
Set point 1/2:
2500 m3/h
...
28
Summary of Contents for VORT NRG EC 3000
Page 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Page 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Page 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Page 54: ...54 NOTE ENGLISH...
Page 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Page 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Page 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Page 101: ...101 IX NOTE FRAN AIS...
Page 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Page 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Page 148: ...148 IX NOTE DEUTSCH...