Chapter 4 CP 240 - serial
Manual VIPA System 200V
4-28
HB97E - CP - Rev. 11/30
Modbus - Parameterization
Byte Function
Range
Default
parameter
0
Baud rate
0h: 9600Baud
6h: 2400Baud
7h: 4800Baud
9h: 9600Baud
Ah: 14400Baud
Bh: 19200Baud
Ch: 38400Baud
0h: 9600Baud
1
Protocol
0Ah: Modbus master ASCII short
0Bh: Modbus master RTU short
0Ch: Modbus slave ASCII short
0Dh: Modbus slave RTU short
1Ch: Modbus slave ASCII long
1Dh: Modbus slave RTU long
Bh: Modbus
master RTU
2 Bit
1/0
Data bits
00b: 5 Data bits
01b: 6 Data bits
10b: 7 Data bits
11b: 8 Data bits
11b: 8 Data bits
Bit
3/2
Parity
00b: none
01b: odd
11b: even
00b: none
Bit
5/4
Stop bits
01b: 1
10b: 1.5
11b: 2
01b: 1 Stop bit
Bit 7/6
reserved
00b: none
3 reserved
0
0
4 Address
1...255
1
5
Debug
0: Debug off
1: Debug on
0
6...7 Wait period
0: automatic calculation
0
1 ... 60000: Time in ms
8 reserved
9 reserved
10 reserved
11 reserved
12 reserved
13 reserved
14 reserved
15 reserved
Note to default parameter!
If no parameterization is present and the CP 240 is linked-up via auto
addressing, the CP has the following default parameters:
Baud rate: 9600Baud, Protocol: ASCII, data bits: 8,
Parity: even
, Stop
bits: 1, Flow control: no, ZNA: 0, ZVZ: 200ms, Receive buffer: 1
Parameter
structure at
Modbus
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...