Chapter 3 Project engineering
Manual VIPA System 200V
3-2
HB97E - CP - Rev. 11/30
Fast introduction
The address allocation and he parameterization of the CP 240 happens by
means of the Siemens SIMATIC Manager in form of a virtual Profibus
system. For this the inclusion of the VIPA_21x.gsd (V. 1.67 or higher) is
required.
For the communication between your CPU and the CP 240 there are
handling blocks available, collected in form a library that you may include
into your Siemens SIMATIC Manager.
•
Start the Siemens SIMATIC Manager with a new project.
•
Include the VIPA_21x.gsd. For this, use a GSD version V. 1.67 or
higher.
•
Include the block library by extracting
FX000011_Vxxx.zip
and de-
archiving VIPA.ZIP.
•
Open the library and transfer the corresponding FCs into your project.
Please follow for the hardware configuration the steps described in the
manual HB97 - CPU:
•
Configure a Profibus-DP master system with the Siemens CPU 315-
2DP (
6ES7 315-2AF03 V1.2)
and create a Profibus subnet.
•
Add to the master system the slave system "VIPA_CPU21x" from the
hardware catalog. This is listed in the hardware catalog under
Profibus-
DP
>
Additional field devices
>
I/O
>
VIPA_System_200V.
•
Assign the address 1 to the slave system. With this, the VIPA CPU
identifies the system as central periphery system.
•
Within this slave system, you place your modules in the plugged
sequence. Start with the CPU at the first plug-in location.
•
Then include your System 200V modules and at the correct place the
CP 240.
•
If necessary parameterize your CP 240.
For the communication a PLC application is required. For this you may use
the following handling blocks:
FC 0 SEND
Data output CPU to CP 240
FC 1 RECEIVE
Receive data from CP 240
FC 8 STEUERBIT
Access at serial modem lines
FC 9 SYNCHRON_RESET Synchronization between CPU and CP 240
FC 11 ASCII_FRAGMENT
Fragmented ASCII data receipt
FC 2 FETCH_RK512
RK512 - FETCH data from remote station
FC 3 SEND RK512
RK512 - SEND data to remote station
FC 4 S/R_ALL_RK512
RK512 - SEND/RECEIVE for passive
station
Overview
Approach
Preparation
Hardware
configuration
PLC program
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...