Chapter 2 Assembly and installation guidelines
Manual VIPA System 200V
2-8
HB97E - CP - Rev. 11/30
Wiring
Most peripheral modules are equipped with a 10pole or an 18pole
connector. This connector provides the electrical interface for the signaling
and supply lines of the modules.
The modules carry spring-clip connectors for the interconnections and
wiring.
The spring-clip connector technology simplifies the wiring requirements for
signaling and power cables.
In contrast to screw terminal connections, spring-clip wiring is vibration
proof. The assignment of the terminals is contained in the description of the
respective modules.
You may connect conductors with a wire cross-section from 0.08mm
2
up to
2.5mm
2
(max. 1.5mm
2
for 18pole connectors).
The following figure shows a module with a 10pole connector.
Note!
The spring-clip is destroyed if you insert the screwdriver into the opening
for the hook-up wire!
Make sure that you only insert the screwdriver into the square hole of the
connector!
Outline
Round aperture
for wires
Rectangular opening
for screwdriver
Pin no.
Pin no.
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...