Manual VIPA System 200V
Chapter 4 CP 240 - serial
HB97E - CP - Rev. 11/30
4-11
The 3964(R) procedure controls the data transfer of a point-to-point link
between the CP 240 and a communication partner. The procedure adds
control characters to the message data during data transfer. These control
characters may be used by the communication partner to verify the
complete and error free receipt.
The procedure employs the following control characters:
•
STX
Start of Text
•
DLE
Data Link Escape
•
ETX
End of Text
•
BCC
Block Check Character (only for 3964R)
•
NAK
Negative Acknowledge
Note!
When a DLE is transferred as part of the information it is repeated to
distinguish between data characters and DLE control characters that are
used to establish and to terminate the connection (DLE duplication). The
DLE duplication is reversed in the receiving station.
The 3964(R) procedure requires that a lower priority is assigned to the
communication partner. When communication partners issue simultaneous
send commands the station with the lower priority will delay its send
command.
only 3964R
STX
DLE
Message-data
DLE
ETX
BCC
Monitor delayed acknowledgment
DLE
Monitor delayed acknowledgment
Active partner
Passive partner
You may transfer a maximum of 250Byte per message.
3964(R)
Procedure
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...