Chapter 5 CP 240 - EnOcean
Manual VIPA System 200V
5-18
HB97E - CP - Rev. 11/30
If ORG = 0x07 (Telegram from a 4 Byte STM sensor):
DATA_BYTE3
Value of third sensor analog input
DATA_BYTE2
Value of second sensor analog input
DATA_BYTE1
Value of first sensor analog input
DATA_BYTE0
Sensor digital inputs as follows:
7 0
Reserved DI_3
DI_2
DI_1
DI_0
If ORG = 0x08 (Telegram from a CTM module set into HRC operation):
DATA_BYTE2..0 always = 0
DATA_BYTE3 as
follows:
7 0
RID UD
PR
SR Reserved
RID
(2 bit)
Rocker ID, from left (A) to right (D): 0, 1,
2 and 3
UD (1
bit)
UD=1
Æ
O-button, UD=0
Æ
I-button
PR (1
bit)
PR=1
Æ
Button pushed, PR=0
Æ
Button
released
SR
(1 bit)
SR=1
Æ
Store, SR=0
Æ
Recall (see
note)
Reserved
(3 bit)
for future use
Note: The SR bit is used only when the lower 3 bits from ID_BYTE0 =
B’111’ (scene switch), and RID
≠
0 (indicates that the memory buttons M0-
M6 are operated in the handheld remote control).
If ORG = 0x0A (Modem telegram):
Please note the different structure of modem telegrams with 6 data bytes
and 2 address bytes for the ID of the receiving modem. See A.1.1.
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...