Chapter 3 Project engineering
Manual VIPA System 200V
3-4
HB97E - CP - Rev. 11/30
Project engineering
The address allocation and he parameterization of the directly plugged
System 200V modules happens by means of the Siemens SIMATIC
Manager in form of a virtual Profibus system. You transfer your project into
the CPU serial via the MPI interface or directly via MMC.
For the project engineering of the CPU a thorough knowledge of the
SIMATIC Manager and the hardware configurator from Siemens is
required!
For the project engineering the following preconditions must be fulfilled:
•
SIMATIC Manager from Siemens is installed at PC res. PG
•
GSD files are included into hardware configurator from Siemens
•
The project can be transferred into CPU (serial e.g. "Green Cable" or
MMC)
•
Start the hardware configurator from Siemens with a new project and
insert a profile rail from the hardware catalog.
•
At the first available slot you place the CPU 315-2DP (6ES7 315-2AF03
V1.2) from Siemens.
•
If your CPU 21x has an integrated Profibus-DP master, you may now
connect it to Profibus and include your DP slaves.
•
Create a Profibus subnet (if not present yet).
•
Add the system "VIPA_CPU21x" to the subnet. You will find this in the
hardware catalog under
PROFIBUS DP
>
Additional field devices
>
IO
>
VIPA_System_200V.
Assign the
Profibus address 1
to this slave.
•
In your configurator, place the CPU 21x, which you are using,
always
on the 1. slot
by taking it from the hardware catalog.
•
Then you include your System 200V modules in the plugged sequence
and your CP 240 at the according place.
•
If necessary parameterize your CP 240.
•
Save your project.
General
Requirements
Hardware
configuration
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...