Chapter 4 CP 240 - serial
Manual VIPA System 200V
4-38
HB97E - CP - Rev. 11/30
Code 06h: Write 1 Word to master output area 4x
Command telegram
Slave address
Function code
Address
word
Value
word
Check sum
CRC/LRC
1 Byte
1 Byte
1 Word
1 Word
1 Word
Respond telegram
Slave address
Function code
Address
word
Value
word
Check sum
CRC/LRC
1 Byte
1 Byte
1 Word
1 Word
1 Word
Code 0Fh: Write n Bits to master output area 0x
Please regard that the number of Bits has additionally to be set in Byte.
Command telegram
Slave address Function
code
Address
1. Bit
Number of
Bits
Number of
Bytes
Data
1. Byte
Data
2. Byte
...
Check sum
CRC/LRC
1 Byte
1 Byte
1 Word
1 Word
1 Byte
1 Byte
1 Byte
1 Byte
1 Word
max.
250
Byte
Respond telegram
Slave address Function code Address
1. Bit
Number of
Bits
Check sum
CRC/LRC
1 Byte
1 Byte
1 Word
1 Word
1 Word
Code 10h: Write n Words to master output area 4x
Command telegram
Slave address Function
code
Address
1
st
word
Number of
words
Number of
Bytes
Data
1. word
Data
2. word
...
Check sum
CRC/LRC
1 Byte
1 Byte
1 Word
1 Word
1 Byte
1 Word
1 Word
1 Word
1 Word
max. 125 Words
Respond telegram
Slave address Function code Address
1. word
Number of
words
Check sum
CRC/LRC
1 Byte
1 Byte
1 Word
1 Word
1 Word
Write 1 Word
06h
Write n Bits 0Fh
Write n Words 10h
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...