Chapter 4 CP 240 - serial
HB97E - CP - Rev. 11/30
4-39
Modbus - Error messages
At the communication at Modbus there are 2 error types:
•
Master doesn’t receive valid data
•
Slave responds with error message
If the slave doesn’t answer within the specified delay time or if a telegram is
defective, the master enters an error message into the receive block in
plain text.
The following error messages may occur:
ERROR01 NO DATA
Error no data
No telegram arrived within the specified delay
time.
ERROR02 D LOST
Error data lost
No data is available because either the receive
buffer is full or an error occurred in the receive
section.
ERROR03 F OVERF
Error frame overflow
The telegram end wasn’t recognized or maximum
telegram length exceeded.
ERROR04 F INCOM
Error frame incomplete
Only a part telegram has been received.
ERROR05 F FAULT
Error frame Fault
The check sum of the telegram is faulty.
ERROR06 F START
Error frame start
The start bit it wrong. this error may only occur
with Modbus-ASCII.
If the slave answers with an error, the function code is sent back like shown
below, marked as “or” with 80h:
DB11.DBD 0
DW#16#05900000
with 05
→
90
→
0000
→
Respond telegram
Slave address 05h
Function code 90h (error message, for 10h
OR 80h = 90h)
The rest data is not relevant, for an error
has been sent.
Overview
Master doesn’t
receive valid data
Slave answers
with error
message
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...