Manual VIPA System 200V
Chapter 5 CP 240 - EnOcean
HB97E - CP - Rev. 11/30
5-11
Addr. Label
Type
Comment
0.0
STRUCT
+0.0
Empfangsfach
STRUCT
Receive data block
+0.0 RX_TX_Kennung
BYTE
0B=RX/6B=TX
+1.0 ORG
BYTE
+2.0
Datenbyte3
BYTE
Data byte 3
+3.0
Datenbyte2
BYTE
Data byte 2
+4.0
Datenbyte1
BYTE
Data byte 1
+5.0
Datenbyte0
BYTE
Data byte 0
+6.0
IDbyte2_3
WORD
ID byte 2 and 3
+8.0
IDbyte0_1
WORD
ID byte 0 and 1
+10.0 Status
BYTE
Status
=12.0
END_STRUCT
+12.0 Reserve
BYTE
+13.0 EMP_LAEUFT
BOOL
Still
receiving
+13.1
LETZTER_BLOCK
BOOL
Last block has been received
+13.2
FEHL_EMPF
BOOL
Error during reception
+14.0
PAFE
BYTE
Parameterization error byte of FC1
+15.0 Res00
BOOL
+15.1 Res01
BOOL
+15.2 Res02
BOOL
+15.3 Res03
BOOL
+15.4 Res04
BOOL
+15.5 Res05
BOOL
+15.6 Res06
BOOL
+15.7
Empfang_fertig
BOOL
Telegram received completely
+16.0
GEEM
WORD
Already received data
+18.0
ANZ_INT
WORD
Amount of received data
+20.0 Reserve1
ARRAY[0..50]
*1.0
BYTE
=72.0
END_STRUCT
DB11
Receive data block
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...